Kim chống sét LPI

  • Kim chống sét hiện đại
  • Phát tia tiên đạo sớm
  • ESE system lightning rod, standardized according norm UNE 21.186. Usefull for external lightning protection to all type of constructions.
  • Norms of applicaton:
    • UNE 21185
    • UNE 21186
    • CEI 1024-1
    • NFC 17 102
    • UNE 50164-1
  • Central shaft and deflection set made in stainless steel. AISI 316.
  • Exciter set: epoxy resine.
  • 100% of efficacy in discharge capture.
  • High level of protection.
  • Electric continuity guaranteed. The device doesn’t offer any resistance to discharge conduction.
  • It preserves its initial properties after each discharge.
  • Not fungible (as it doesn't include electronic elements).
  • It doesn’t need external power supply. 
  • Operation guaranteed in any atmospheric condition

INGESCO® PDC Lightning rod

We obtain the Early Streamer Emission time (Dt) through the laboratory tests (UNE 21186, annex C). Then, applying the formulas and prescriptions of different norms, we can calculate the radius of the protection area of each model.

In Spain the valid law is, from October 2006, the Código Técnico de la Edificación which give us the following results for INGESCO® PDC:

  • PDC 3.1 PDC 3.3 PDC 4.3 PDC 5.3 PDC 6.3
  • LEVEL I (D=20 m) 35 m 45 m 54 m 63 m 74 m
  • LEVEL II (D=30 m) 45 m 55 m 64 m 73 m 84 m
  • LEVEL III (D=45 m) 60 m 70 m 79 m 88 m 99 m
  • LEVEL IV (D=60 m) 75 m 85 m 94 m 103 m 114 m

Internationally, the reference norm is NFC 17 102 which give us the following results for INGESCO® PDC.

  • PDC 3.1 PDC 3.3 PDC 4.3 PDC 5.3 PDC 6.3
  • LEVEL I (D=20 m) 35 m 45 m 54 m 63 m 74 m
  • LEVEL II (D=45 m) 54 m 65 m 74 m 84 m 95 m
  • LEVEL III (D=60 m) 63 m 75 m 85 m 95 m 106 m

These radius of protection have been calculated for a height of 20 meters.